Dynasty TEL 12-90. Call for volume pricing.
Valve Regulated Lead Acid Battery for
Communications Standby Power Applications
In critical standby power applications, maximum battery life is
essential. Dynasty long duration batteries deliver this while complying
with rigorous industry standards. Computer modeling, stringent
components materials selection and design criteria as well as
state-of-the-art automated manufacturing are all validated through
extensive life-cycle testing and years of in-service life in
telecommunications and uninterruptible power systems applications.
- Flame-arresting one-way pressure-relief vent for safety and long life
- Thermally welded case-to-cover bond to ensure a leakproof seal
- Flame-retardant polypropylene case and cover compliant with UL94 V-0 with a Limiting Oxygen Index of greater than 28
- Absorbent Glass Mat (AGM) technology for efficient gas recombination of 99% plus
- Thick positive plate design for maximum service float life - 10 year design life
Specification
- 72 lbs. / 33 kg.
- dimensions (inches): 13.42 long x 6.80 deep x 8.59 high
- 88 Ah @ 8 hour rate to 1.75 volts per cell @ 77 F (25 C)
- 85.5 Ah @ 10 hour rate to 1.80 volts per cell @ 20 C (68 F)
- Operating Temperature Range Discharge; -40 F ( -40 C to +160 F (71 C)
- Charge; -10 F (-23 C) to +140 F (60 C)
(with temperature compensation)
- Nominal Operating Temperature Range +74 F (23C) to +80 F (27 C)
- Float Charging Voltage 13.5 to 13.8 VDC/unit Average @ 77 F (25 C)
- Recommended Maximum Charging Current Limit C/5 amperes (5.8 amps @ 100% depth of discharge)
- Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
- Maximum voltage allowed = 4% P-P
- Maximum current allowed = 1.65 amperes RMS (C/20)
- Self Discharge Dynasty Telecom batteries may be stored for up
to 6 months at 77F (25 C) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.
Accessories