| Application |
| Power Rating/Size (kVA) |
10, 20, 30, 50 75, 100, 150, 200, 300, 500, 750, 1,000 typical – up to 1,500 kVA available |
| Phase - Frequency (Hz) |
Three phase only- 50 or 60 Hz |
| Voltages |
120, 208, 220, 240, 380, 400, 440, 480, 600 are typical. Custom voltages available |
For voltage step up or step down contact factory |
| Connections |
3 wire input and output |
| Cable Entry |
Side, back, top bottom, depending on enclosure type – contact factory for details |
| Sag Correction/Regulation |
| Sag Correction |
1 or 2 phase sags - to 30% remaining voltage (-70% sag) corrected to 95% of nominal
3 phase sags - to 60% remaining voltage (-40% sag) corrected to 95% of nominal |
| Output Regulation |
±5% [Note: unit normally operates in bypass mode until voltage drops to a trigger point of 90% of nominal voltage, at which time correction is initiated] |
| Phase Shift Correction |
Phase shifts are corrected automatically during sag correction |
| Correction Duration |
No limitation on length or frequency of sag correction, no recharge time |
| Harmonic Distortion |
No distortion added in bypass mode |
| Surge Suppression |
| Surge Suppression |
Tested to ANSI/IEEE standard C62.41 |
| Operating Characteristics |
| Overload/Inrush Capability |
6000% -1 cycle, 1000% - 1 second, 500% - 5 seconds, 200% - 1 min. ; 1000% fault clearing |
| Minimum Load |
No minimum load |
| Load Power Factor |
No limitations, compatible with all load types |
| Response Time |
2 milliseconds (1/8 cycle @ 60 Hz) |
| Efficiency |
99% during normal operation |
| Operating Frequency |
Conforms to NERC standards |
| Unit/Load Protection |
| Circuit Breaker |
Input circuit breaker standard |
| Failsafe Electronic Bypass |
Actuates on overtemperature, overcurrent, component failure without loss of load |
| Construction |
| Technology |
Inverter-based series voltage injection |
| Enclosure |
NEMA 1 standard |
| Display |
Touchscreen display with event log, unit status, fault log |
| Cooling |
Natural convection (forced air cooling of inverter used in larger units) |
| Environmental |
| Audible Sound Level |
Meets NEMA standards |
| Ambient Temperature |
32 to 104°F (0 to 40°C) |
| Relative Humidity |
0-95% non-condensing |
| Operating Altitude |
0 to 10,000 ft (3000m) |
| Common Options |
| Instrumentation |
Ammeter, voltmeter, power monitor with or without Modbus® communications capability |
| Adjustable Trigger Point |
Manually adjustable trigger point |
| Enclosures |
Enclosures NEMA 12, NEMA 3R, etc. up to stainless steel NEMA 4X available |
| Maintenance Bypass |
Manual mechanical bypass to isolate unit |