LDP20-120-1
Model LDP20-120-1
for 120 VAC, 2-Wire + Ground
- SPD Category and Type: Service entrance or service panel, permanently connected.
Intended for use on U.S., TN-C, TN-C-S and TNS neutral grounding.
- Technology: Multiple Metal Oxide Varistors, with individual current fusing and thermal
disconnects for each MOV. LED indicates proper functioning of L-N MOVs.
- Service Amperage / Fault Current: 200 A max / 10,000 A max short circuit current. If a dedicated
breaker is used, it should be >20A at main panel or >10A at subpanel.
- Connection Means: In parallel across mains or behind breaker.
- Maximum Continuous Operating Voltage, 50-60 Hz, L-N: 138 VAC
- Protection Modes: L-N N-G
- Varistor MCOV: 150 VAC
- Varistor Voltage at 1 mADC: 240 V
- Leakage, L-N at 120 VAC: <250 mA
- Maximum Surge Current, Single Pulse, 8/20 ms: 20 kA
- Suppression Voltage L-N, N-G 500 A, 100 kHz (6 kV): 445 V
- Suppression Voltage L-N, N-G 500 A, 8/20 s (6 kV): 420 V
- Suppression Voltage L-N, N-G 3 kA, 8/20 s (6 kV): 480 V
- Suppression Voltage L-N, N-G 10 kA, 8/20 s (20 kV): 690 V
- UL 1449 Suppression Voltage, L-N: 500 V
- Surge Energy Capability, total: 1360 joules
- Surge Life, 120 VAC L-N applied 3 kA 8/20 s: 3000 times
- Surge Life, 120 VAC L-N applied 10 kA 8/20 s: 75 times
- Component Response Time: <1 ns
- Operating Temperature: -40 to +80 C
- Operating Altitude: 5000 m
- Shipping Weight: .5 kg
- Safety Approvals: UL and cUL Listed per UL1449 and Canadian Codes, File No. E74944
Please call us at 800-876-9373, or
email us for pricing and availability.