EX 7RT (86070)
EX RT 7 kVA
Model Number 86070 Standard Pack without XFMR
Power Rating (VA/W) 7000VA / 4900W
On-Line double conversion with PFC
Input-voltage window 155 - 280VAC at 100% rated load or 120
- 280VAC at 70% of rated load
Frequency 40-70 Hz
Output voltage / Frequency 200 / 208 / 230 / 240 / 250
Volts / 50 / 60 Hz autoselect
Typical runtime (minutes) 70% 100% 21 / 12 minutes
1 Power Module + 1 EXB 12 / 7 minutes
1 Power Module + 2 EXB 30 / 20 minutes
1 Power Module + 6 EXB 118 / 72 minutes
Input / output connection Hardwire
Communication Port Type: 6 voltage free dry contacts DB-9
rated at 2 A 48V DC, (1) RS 232, (1) RJ 45 for RPO (Remote
Power Off) Slot: 1 slot for MGE transverse communication card
(HTTP, XML, Webcard, Jbus)
Dimensions H x W x D (in) and Weight (lbs) Standard
EX RT (Power Module + Battery Module) Form Factor 10.32 (6 U)
X 17.49 X 25 / 192, for 5/7 kVA System, 211 for 11kVA Systems
Standard EX RT with Network Pack Form Factor 10.32 (6 U) X
17.49 X 25 / 209 for 5/7kVA System, 229 for 11kVA System
Power module EX RT 5.16 (3 U) X 17.49 X 25 / 49.6 for
5/7kVA System, 60.6 for 11kVA System
Battery module EXB RT 5.16 (3 U) X 17.49 X 25 / 142 for
5/7kVA System, 151 for 11kVA System Charger module EX RT CLA
5.16 (3 U) X 17.49 X 25 / 26.5 Transformer module EX RT 5.16
(3 U) X 17.49 X 28 / 151