EX 11RT (86205)


EX 11RT (86205)

EX RT 11 kVA

Model Number 86205 EXRT Standard Pack with XFMR

Power Rating (VA/W) 11000VA / 8000W

On-Line double conversion with PFC

Input-voltage window 155 - 280VAC at 100% rated load or 120 - 280VAC at 70% of rated load

Frequency 40-70 Hz

Output voltage / Frequency 200 / 208 / 230 / 240 / 250 Volts / 50 / 60 Hz autoselect

Typical runtime (minutes) 70% 100% 21 / 12 minutes

1 Power Module + 1 EXB 9 / 5 minutes

1 Power Module + 2 EXB 20 / 14 minutes

1 Power Module + 6 EXB 87 / 53 minutes

Input / output connection Hardwire

Communication Port Type: 6 voltage free dry contacts DB-9 rated at 2 A 48V DC, (1) RS 232, (1) RJ 45 for RPO (Remote Power Off) Slot: 1 slot for MGE transverse communication card (HTTP, XML, Webcard, Jbus)

Dimensions H x W x D (in) and Weight (lbs) Standard EX RT (Power Module + Battery Module) Form Factor 10.32 (6 U) X 17.49 X 25 / 192, for 5/7 kVA System, 211 for 11kVA Systems

Standard EX RT with Network Pack Form Factor 10.32 (6 U) X 17.49 X 25 / 209 for 5/7kVA System, 229 for 11kVA System

Power module EX RT 5.16 (3 U) X 17.49 X 25 / 49.6 for 5/7kVA System, 60.6 for 11kVA System

Battery module EXB RT 5.16 (3 U) X 17.49 X 25 / 142 for 5/7kVA System, 151 for 11kVA System Charger module EX RT CLA 5.16 (3 U) X 17.49 X 25 / 26.5 Transformer module EX RT 5.16 (3 U) X 17.49 X 28 / 151