The Power Experts

FIAMM 4 SLA 200

The FIAMM 4 SLA 200 VRLA battery uses VRLA Technology with 99% internal recombination efficiency. The SLA (sealed lead acid) series is non-spillable and maintenance-free and uses AGM (Absorbed Glass Mat) technology.

FIAMM 4 SLA 200 Specifications

Nominal Voltage: 4V
Capacity at 68°F: 200Ah
Short Circuit Current: 3800A
Internal Resistance:  1.00 mohm
Dimensions: 9.84 in L x 7.95 in W x 8.90 in H
Weight: 57 lbs

SLA Series General Specifications

Float Voltage: 2.27 V/cell at 68°F
Boost Voltage: 2.40 V/cell
Float Voltage Compensation with Temperature: -1.39 mV/cell/°F
Self-Discharge at 68°F: <2%/month

SLA Series Standards

IEC 60896 Part 21 – VRLA methods of testing
IEC 60896 Part 22 – VRLA requirements
BS 6290 Part 4 – specifications for VRLA classification
Telcordia GR-4228 – VRLA battery string certification
BS 6334 / UL 94 V0 / IEC 707 FV0 determination of materials flammability
Bellcore TR-NWT-000766 – VRLA battery generic requirements
UL 1778 – UPS equipment
Eurobat > “12 years VERY LONG LIFE”

For more in-depth information, see the data sheet.

For more information about the FIAMM SLA Series,
call 800-876-9373 or email sales@power-solutions.com.