STULZ CyberRow

STULZ CyberRowSTULZ CyberRow systems are ideal for high density, row-based data center cooling in open or contained architectures.  With intelligent airflow control, STULZ CyberRow offers more efficient rack cooling and targeted hot spot reduction.  Close coupling the CyberRow equipment with the server racks increases energy efficiency and the shorter, more predictable air path ensures that no cooled air is wasted.

With the widest range of units and the largest cooling capacity in the industry, STULZ cooling provides adjustable air volume based on real time cooling requirements at the lowest energy consumption.  STULZ E² controller allows for independent valve and fan control so the unit can be adjusted immediately and precisely to varying heat loads and optimize energy efficiency.

STULZ CyberRow Applications

  • High-density racks and hot spots
  • Any size data center, including modular
  • Water-Side economization
  • IT and Telecommunications

STULZ CyberRow Features

  • Available in 12” and 24” cabinet widths
  • Both front discharge and diverted plenum discharge available
  • EC fan technology with independent control for optimum adaptation to air temperatures
  • STULZ E2 Control and Monitoring networking capable and supports universal BMS interface for precise control of temperature and humidity

STULZ CyberRow Benefits

  • Can be used with racks from any manufacturer
  • Innovative technology and high-quality components for minimal energy consumption
  • High performance value in the smallest space
  • Precise temperature control
  • Available in chilled water, air, water, and glycol cooled systems
  • Complete system separation between rack and A/C unit for maximum reliability
  • Made in the USA

STULZ CyberRow Specifications

Capacity CW DX
Model CRS-090 12″ CRS-180 24″ CRS-042 12″ CRS-084 12″ CRS-090 12″
13 – 37 kW 31 – 75 kW 16 kW 31 kW 33 kW
44 – 126 MBH 106 – 256 MBH 55 MBH 106 MBH 112 MBH
4 – 11 Tons 9 – 21 Tons 5 Tons 9 Tons 9.3 Tons
2,900 CFM 5,800 CFM 1,500 CFM 2,900 CFM 2,900 CFM