The Trystar eLITE Model ELE, 5.3kW – 18kW, is a modular, no-break, front access, single phase centralized emergency lighting inverter that provides conditioned and regulated power to normally on and normally off fixtures. The Model ELE is listed to “UL 924 Emergency Lighting Equipment,” “UL 924 Auxiliary Lighting and Power Equipment,” and “UL 1778 Uninterruptible Power Supplies” standards. The Model ELE is also compliant with NFPA 101 and NFPA 111 requirements for testing of emergency lighting inverter systems.
The Model ELE is compatible with LED drivers/fixtures and is a perfect choice when a larger kW-rated single phase emergency power source is required, up to and including 18kW.
Trystar eLITE Model ELE Features
- Automatic self-testing, data logging, and reporting per NFPA 101 – 7.9.3.1.3.
- Uninterrupted, regulated, continuous sine wave output for use with “normally on” lighting fixtures and exit lamps
- True no-break system, providing voltage regulation and performance characteristics that extend ballast, LED driver, and lamp life
- Standby output for use with “Normally Off” lighting fixtures
- Front access, modular cabinet construction
- Integral constant voltage transformer isolates and regulates output voltage
- Delivers highly filtered and spike-free power to emergency lighting fixtures and “Life Safety” devices
- Overload and short-circuit proof
- Front access distribution, with lockable drop-down panel door
- Standard AC and DC input protection
- Generator compatible
- NEMA1 enclosure
- Internal make-before-break bypass switch
- Optional zone sensing
- Optional control device override (wall switch, occupancy sensor, dimmer, etc.)
- Optional CB trip indicator alarm/light
- Electrically isolated output
- Advanced monitoring system
- Optional NetMinder Ethernet/MODBUS adapter for network monitoring
Trystar eLITE Model ELE Specifications
- Input Operating Voltage Range: +10%, -15% without battery usage
- Input Frequency: 60 Hz, ± 2.5 Hz
- Input Current Harmonic Distortion: Less than 10%
- Power Factor: Self-correcting to > 0.95
- Output Sine wave Voltage: Maximum 3% harmonic distortion, any single harmonic
- Output Voltage Regulation: Typically better than ± 3%
- Isolation: Galvanic
- Standard Unit Operating Temperature: 0°C to 40°C
- Total System MTBF: 100,000 hours
- Common Mode Noise Rejection: 120 dB
- Transverse Mode Noise Rejection: 70 dB
- Efficiency: 90% typical
For more in-depth specifications, see the data sheet.