eLITE Model ELN Emergency Lighting Inverters UL 924

eLITE Model ELN Emergency Lighting Inverters UL 924eLITE Model ELN Emergency Lighting Inverters UL 924, 550W to 1.5kW, by Controlled Power,  meet the NFPA 101 and NFPA 111 standards, and are considered “Life Safety Equipment.” The Model ELN is also UL 924 listed as “Emergency Lighting Equipment,” providing the required 90 minutes of emergency backup power.

With a front-access design and a small footprint, the Model ELN is suited for wall or floor-mounted installations. The Model ELN is compatible with LED drivers/fixtures, and is a perfect choice when providing emergency power to fan motor loads that are a part of the life safety system.

eLITE Model ELN Features

  • Listed UL 924 “Emergency Lighting Equipment” and “Auxiliary Lighting and Power Equipment”
  • Meets NFPA 101 and NFPA 111 standards, including SEPSS (Stored Electrical Energy Emergency and Standby Power Systems)
  • Uninterrupted, regulated, continuous sine wave output for use with “Normally On” lighting fixtures and exit lamps
  • Standby output for use with “Normally Off” lighting fixtures
  • Programmable, timed “Normally Off” and “Normally On” outputs
  • Integral constant voltage transformer isolates and regulates output voltage
  • True no-break system, providing voltage regulation and performance characteristics that extend ballast, LED driver, and lamp life
  • System approved for 42k AIC rated source
  • Integral status and alarm panel
  • Front-access design and small footprint are ideal for wall- or floor-mounted installations
  • Standard NEMA 2 drip-proof enclosure
  • Remote communications via alarm signals or RS232
  • Generator-compatible
  • Optional remote status panel
  • Optional NetMinder Ethernet/MODBUS adapter for network monitoring

eLITE Model ELN Specifications

  • Input Operating Voltage Range: +10%, -40% typical, load-dependent, without battery usage
  • Input Frequency: 60 Hz, ± 2.5%
  • Output Sine Wave Voltage: Maximum 3% harmonic distortion, any single harmonic
  • Power Factor: Self-correcting to >0.95
  • Line Voltage Regulation: ± 3%
  • Load Regulation: Typically better than ±3%
  • Isolation: Galvanic
  • Standard Unit Operating Temperature: 0°C to +40°C
  • Total System MTBF: 100,000 hours
  • Common Mode Noise Rejection: 120 dB
  • Transverse Mode Noise Rejection: 70 dB
  • Efficiency: 89% typical

For more in-depth specifications, see the data sheet.

Single Phase Sizes: 550W, 1kW, 1.5kW

For more information about Controlled Power Emergency Lighting Inverters,
call 800-876-9373 or email sales@power-solutions.com.