The Eaton 93T UPS, 50–60 kW, combines superior performance with easy installation and operation and a small footprint. ideal for IT applications like small data centers, server rooms and mission critical applications like commercial and institutional, finance, healthcare, government and industrial.
The 93T accessory cabinet designs allow installations on either side of the UPS, giving you flexibility in floor space usage. The friendly graphical 7-inch LCD touchscreen interface provides visibility and you can view system status from a distance with the blue/yellow/red LED light bars. The modular power module design ensures lowest mean time to repair (MTTR) if there ever is an issue. Firmware scalability allows future kW upgrade. Reduce power and cooling OPEX with the three-level inverter.
Manage your power devices in your physical or virtual environment with Eaton’s Brightlayer™ Software suite. Increase uptime through 24×7 remote monitoring and reporting capabilities using Eaton’s PredictPulse™ service that alerts technicians during critical events and results in faster resolutions when a problem is detected.
Eaton 93T UPS Features
- Top cable entry is standard; cable entry is also available at the rear or on the optional maintenance bypass cabinet.
- Built-in device and host USB
- Two communication slots
- 7-Inch color touchscreen LCD interface
- Slide out power modules (20 kW), static switch internal to power module
- Internal batteries
Eaton 93T Specifications
| Specifications | Details |
| Power Ratings | 15,20,30,40,60,80,100,120,160, 200 kW |
| Voltage Range (Vac) | 380/400/415V |
| Input Voltage Range (Vac) | 201-478 |
| Power Factor | >0.99 |
| Input Current Distortion | <3% |
| Frequency | 50/60 Hz |
| Battery Type | Lithium, VRLA, Ni-Cad |
| Battery Voltage | 320V-607V |
| Parallel Capability | Up to 4x parallel |
| Efficiency | >96% in online mode, up to 99% with ESS |
| Voltage THD | <2% (100% linear load), <5% (non-linear load) |
| Overload Capacity | 110% – 60 min, 125% – 10 min, 150% – 1 min |
| Crest Factor | 3:01 |
| Operating Temperature | 0°C to 40°C |
| Noise Level | <65 dBA |
| Back feed protection | Built-in |
| Operating Temperature / Humidity | 0-40 degree C without derating / 5-95% RH, non-condensing |
| Display | 15-80kVA: 5” Touchscreen Color display |
| 100-200kVA: 7’’ Touchscreen Color display | |
| Connectivity Options | Gigabit network card, Industrial gateway card, EMP temperature and humidity sensor; AS/400 relay/RS-232 interface card, RS232& USB |
| Dimensions (W x D x H mm) | 15-40 kW: 330 x 657 x 528 |
| 60 – 80 kW: 330 x 690 x 986 | |
| 100 -120 kW: 500 x 850 x 1260 | |
| 160 – 200 kW: 550 x 850 x 1600 |
For more in-depth specifications, see the data sheet.
For more information about the Eaton 93T UPS,
call 800-876-9373 or email [email protected].