1.800.876.9373

Newmar Outdoor UPS

UPS Systems | Newmar Outdoor UPS

Newmar Outdoor AC UPSThe Newmar Outdoor UPS Series provides critical equipment with a secure source of clean AC power during utility grid failures and brownouts. Engineered to meet the demanding applications and harsh environments of outdoor cabinets, traffic, and Intelligent Transportation Systems (ITS), public safety, and remote communication sites; the Rugged AC UPS features a wide AC input voltage range of 88 – 152V AC and operates at extreme hot and cold temperatures.

This line-interactive UPS features wide range Automatic Voltage Regulation (AVR) allowing the AC UPS to stay in normal operation without transferring to back-up mode during temporary voltage irregularities and preserving and extending battery life cycle. The indoor/outdoor UPS models also contain temperature-compensated battery charging which enhances battery life.

Newmar Outdoor UPS Features

  • Wide range of Automatic Voltage Regulation (AVR)
  • Temperature compensated charging
  • Fast transfer time < 5ms typical
  • SNMP network card, RS-232 and USB ports included
  • LCD screen for quick access to system diagnostics
  • Front panel connections for easy install
  • Forced air cooled with fan filter (field replaceable)
  • Alarm contacts (six sets)
  • 19” rack or cabinet mounting
  • AC Wiring: hard wired AC input/output

Newmar Outdoor UPS Specifications

ModelOutput VA/Watts
Continuous
Power
Factor
Nominal
Battery
Voltage
Dimensions
(H x W x D)
System Weight 
AC-UPS-24-700700/700124V DC5.23” x 15.75” 9.45”23 lbs
AC-UPS-48-12001200/1200148V DC5.23” x 15.75” 9.45”28.6 lbs
AC-UPS-48-20002000/1600148V DC5.23” x 15.75” 9.45”28.6 lbs

Additional Specifications

Input Voltage Range: 88 – 152V AC, User Programmable. Default set @ 100 – 130V AC
Transfer time (typical): UPS Mode: 5ms / Normal Mode: 20ms / Generator Mode: 25ms
Site Fault Detection: Yes
Efficiency: Line Mode: 95% / AVR Mode: 90% / UPS Inverter Model: >90%
Output Waveform: Pure sine wave
Nominal Output Voltage: 120V AC, +/- 5%
Output Frequency: 50/60 Hz +/- 0.1%
Nominal DC Voltage: 48V DC (2000V A and 1200V A) / 24V DC (700V A)
Low DC Voltage Warning: 48V DC: 42 – 55V DC (adjustable) / 24V DC: 21 – 27.5V DC (adjustable)
No Load Power Consumption: 28 watts at rated nominal DC Voltage THD (Bat. Mode) <3% (full resistive load)
Load Crest Factor: 3:1 @ rated load
Output Short Circuit Protection: Output breaker/electronic current limit/firmware
Surge Capacity: 200% (rated power for 5 secs)
Back Feed Protection: Yes
Operating Temperature: -40° to 80° C
Storage Temperature: -50° to 80° C
Relative Humidity: 5 to 95% non-condensing

See our Custom Outdoor UPS page for information about outdoor UPS systems designed to meet specialized requirements.

 

For more information about Newmar UPS Systems,
call 800-876-9373 or email [email protected].