The C&D TEL 12-105FNS/FNSG has been discontinued. The C&D TEL 12-115FS is an ideal replacement.
TEL Series True Front Access Float Service – C&D TEL 12-105FNS/FNSG
- Long life float service design with premium alloy and material components
- True Front Access (TFA) design
- Optional TFA gas collection system
- True direct connect terminal for reliability
- C&D Ohmic Ring for accurate testing
- Superior output due to direct terminal connection
- Compliant to major global specifications
C&D TEL 12-105FNS/FNSG Specifications
- 71 lbs. / 32kg
- Dimensions (inches): 16.1 long x 4.1 wide x 11.2 high
- Capacity 104 Ah @ 8 hour rate to 1.75 volts per cell @ 77 F (25 C)
- Operating Temperature Range Discharge; -40 F (-40 C) to +160 F (71 C)
- Nominal Operating Temperature Range +68 F (20C) to +80 F (27 C)
- Float Charging Voltage 13.5 to 13.8 VDC/unit Average/12V @ 77 F (25 C)
- Recommended Maximum Charging Current Limit C20/5 amperes
- Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
- Batteries may be stored for up to 6 months at 77F (25 C) and then a freshening charge is required. For higher temperatures the time interval will be shorter.
Weight: 71.00 pounds.
For more information about C&D Batteries,
call 800-876-9373 or email [email protected].