C&D TEL 12-105FNS/FNSG

TEL-12105FNS

The C&D TEL 12-105FNS/FNSG has been discontinued. The C&D TEL 12-115FS is an ideal replacement.

TEL Series True Front Access Float Service – C&D TEL 12-105FNS/FNSG

  • Long life float service design with premium alloy and material components
  • True Front Access (TFA) design
  • Optional TFA gas collection system
  • True direct connect terminal for reliability
  • C&D Ohmic Ring for accurate testing
  • Superior output due to direct terminal connection
  • Compliant to major global specifications

C&D TEL 12-105FNS/FNSG Specifications

  • 71 lbs. / 32kg
  • Dimensions (inches): 16.1 long x 4.1 wide x 11.2 high
  • Capacity 104 Ah @ 8 hour rate to 1.75 volts per cell @ 77 F (25 C)
  • Operating Temperature Range Discharge; -40 F (-40 C) to +160 F (71 C)
  • Nominal Operating Temperature Range +68 F (20C) to +80 F (27 C)
  • Float Charging Voltage 13.5 to 13.8 VDC/unit Average/12V @ 77 F (25 C)
  • Recommended Maximum Charging Current Limit C20/5 amperes
  • Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
  • Batteries may be stored for up to 6 months at 77F (25 C) and then a freshening charge is required. For higher temperatures the time interval will be shorter.

Weight: 71.00 pounds.

For more information about C&D Batteries,
call 800-876-9373 or email [email protected].