PDI PowerHub 2 PDU

PDI PowerHub The PDI PowerHub 2 PDU, by PDI, an Eaton Company, is a powerhouse unit and is available in sizes ranging from 375 – 1.25 MVA.  The 60” wide x 40” deep, true, front-access cabinet is the smallest footprint in its class.  Known for its centralized brazed bus system, the PowerHub 2 provides up to either (12) 400A or (16) 225A 100% rated, sub feed distribution breakers.  It’s compartmentalized design isolates controls and high voltage components for simplified maintenance and increased operator safety.  Front Access Infrared Scanning ensures maximum reliability and uptime for your mission critical facility. For proactive management of power usage and availability, the PowerHub 2 utilizes Intelligent Power Monitoring through the WaveStar® BCMS, or Branch Circuit Monitoring System including a class-leading 7” color touchscreen display.

PDI PowerHub 2 Features

  • Four-tier True Front Access Cabinet: The 60″ wide x 40″ deep Four-tier True Front Access Cabinet maximizes square footage utilization and enables all operation, maintenance and service from the front of the PDU
  • Front Access Infrared Scanning: Full swing out front doors and an unobstructed view cabinet design enable infrared scanning of all bolted line and load connections
  • 375 to 1MVA DOE2016 TransformerPowerHub 2 offers DOE-compliant transformers in sizes from 375 to 1MVA, up to 1.25 MVA High Efficiency Transformer
  • Future-Proof Dual and Triple Output Transformer: PowerHub 2 offers dual and triple output transformers allowing easy migration to different voltages, future-proofing your data center
  • Compartmentalized Controls & High Voltage Enclosures: Isolated compartments for both controls and high voltage components simplifies maintenance and increase operator safety
  • Intelligent Power Monitoring: PDI’s Branch Circuit Monitoring System (BCMS) allows for the pro-active management of power usage and availability
  • Brazed Transformer Connections: Brazed transformer connections decrease electrical resistance and eliminate the need for transformer infrared scanning
  • Centralized Bus Design: PowerHub 2 provides up-to 12 (400A) and up-to 16 (225A) sub feed distribution breakers via a centralized bus design
  • Adaptable Service Entrances: Landing service entrance cables has never been easier with Top/Bottom Entry/Exit configurations

PDI PowerHub 2 Specifications

kVA Rating375kVA – 1.25MVA
Input3-phase, 3-wire plus ground
Input Voltage
@ 50 Hz: 380V – 415V
@ 60 Hz: 600, 480 or 208V
Output3-phase, 4-wire plus ground
Output Voltage
@ 50 Hz: 380/220, 400/231, 415/240VAC
@ 60 Hz: 600/346, 575/332, 480/277, 415/240VAC or  208/120VAC
Listed to UL1062, UL 1950, CSA Certified
Operating TemperatureAmbient 0°C to 40°C
Relative Humidity0% to 95% non-condensing
Altitude≤ 6,600 ft.
50 Hz Operating Range47-53 Hz
60 Hz Operating Range57-63 Hz
Storage TemperatureAmbient -10°C to +40°C

For more in-depth specifications, see the data sheet.