Eaton 93T UPS

UPS Systems | Eaton UPS Systems | Eaton 93T UPS

Eaton 93T UPSThe Eaton 93T UPS, 50–60 kW, combines superior performance with easy installation and operation and a small footprint. ideal for IT applications like small data centers, server rooms and mission critical applications like commercial and institutional, finance, healthcare, government and industrial.

The 93T accessory cabinet designs allow installations on either side of the UPS, giving you flexibility in floor space usage. The friendly graphical 7-inch LCD touchscreen interface provides visibility and you can view system status from a distance with the blue/yellow/red LED light bars. The modular power module design ensures lowest mean time to repair (MTTR) if there ever is an issue. Firmware scalability allows future kW upgrade. Reduce power and cooling OPEX with the three-level inverter.

Manage your power devices in your physical or virtual environment with Eaton’s Brightlayer™ Software suite. Increase uptime through 24×7 remote monitoring and reporting capabilities using Eaton’s PredictPulse™ service that alerts technicians during critical events and results in faster resolutions when a problem is detected.

Eaton 93T UPS Features

  • Top cable entry is standard; cable entry is also available at the rear or on the optional maintenance bypass cabinet.
  • Built-in device and host USB
  • Two communication slots
  • 7-Inch color touchscreen LCD interface
  • Slide out power modules (20 kW), static switch internal to power module
  • Internal batteries

 

Eaton 93T Specifications

SpecificationsDetails
Power Ratings15,20,30,40,60,80,100,120,160, 200 kW
Voltage Range (Vac)380/400/415V
Input Voltage Range (Vac)201-478
Power Factor>0.99
Input Current Distortion<3%
Frequency50/60 Hz
Battery TypeLithium, VRLA, Ni-Cad
Battery Voltage320V-607V
 Parallel CapabilityUp to 4x parallel
Efficiency>96% in online mode, up to 99% with ESS
Voltage THD<2% (100% linear load), <5% (non-linear load)
Overload Capacity110% – 60 min, 125% – 10 min, 150% – 1 min
Crest Factor3:01
Operating Temperature0°C to 40°C
Noise Level<65 dBA
Back feed protectionBuilt-in
Operating Temperature / Humidity0-40 degree C without derating / 5-95% RH, non-condensing
Display15-80kVA: 5” Touchscreen Color display
100-200kVA: 7’’ Touchscreen Color display
Connectivity OptionsGigabit network card, Industrial gateway card, EMP temperature and humidity sensor; AS/400 relay/RS-232 interface card, RS232& USB
Dimensions (W x D x H mm)15-40 kW: 330 x 657 x 528
60 – 80 kW: 330 x 690 x 986
100 -120 kW: 500 x 850 x 1260
160 – 200 kW: 550 x 850 x 1600

For more in-depth specifications, see the data sheet.

For more information about the Eaton 93T UPS,
call 800-876-9373 or email [email protected].