Trystar SureImage Model Ultra-K/M

Trystar SureImage Model Ultra-K/MThe Trystar SureImage Model Ultra-K/M, Medical-Grade, is a medical-grade, high-efficiency, K-rated, power conditioning transformer specifically designed to provide a high degree of electrical noise attenuation and transient voltage suppression to MRI, CT, PET, Linear Accelerator, and X-ray equipment. The Ultra-K/M provides isolation from the incoming power source and also provides output power conditioning. These attributes protect medical imaging and treatment equipment from spikes, harmonics and ground noise, thus ensuring accurate and clear image scans.

The Ultra-K/M is 75K(i) – 225K(i)) The K(i) rating refers to the intermittent kVA or momentary power demand rating.

The Ultra-K/M meets and exceeds the high efficiency levels defined by the U.S. Department of Energy 2016 Standard, thus providing energy savings under both linear and non-linear loads.

Trystar SureImage Model Ultra-K/M Features

  • Significant Reduction/Elimination of “Artifacts” in the Digital Image
  • Enhanced Workflow and Processing Time
  • Prevents Premature Failure of Imaging/Treatment Equipment
  • Lower Cost to Maintain Imaging/Treatment Equipment
  • Reduced Installation Expenses
  • Higher Power Efficiency and Lower Operating Costs

Trystar SureImage Model Ultra-K/M Specifications

  • Efficiency: Meets and exceeds U.S. Dept. of Energy (DOE) 2016 minimum efficiency standards identified under DOE 10 CFR Part 431.
  • Transformer Shielding: Triple (3 electrostatic shields)
  • Output Load Regulation: ≤ 2% from typical steady state load to intermittent power demand
  • Voltage Compensation Taps: Full capacity taps at 2.5% increments, 2 FCAN and 4 FCBN (Exception: 225K(i) at 208 VAC or 240 VAC input — taps at 5% increments, 1 FCAN and 2 FCBN)
  • K-Factor Rating: K13
  • Output Impedance: 2% typical at 50% of rated load
  • Common Mode Noise Attenuation: 146 dB
  • Transverse Mode Noise Attenuation: 3 kB down at 10 KHz, 40 dB down per decade
  • Standard Surge Protection Device (SPD): Secondary-connected, 40kA per mode; with high frequency filter, status indicator
  • Temperature Rise: 115°C above ambient, not exceeding 135°C under non-linear loading, per UL 1561 Standard
  • Optional SPD, 100kA per phase, UL 1449 Listed; with EMI/RFI filtering, form C relay contacts, LED status indicators
  • Optional main input/output CB provided in separate NEMA1 enclosure for external mounting and installation
  • Optional high/over temperature alarm contacts for customer’s hardwired connection
  • Optional IR window for safe routine thermal scanning of transformer connections under load

For more in-depth specifications, see the data sheet.

For more information about Trystar Power Products,
call 800-876-9373 or email [email protected].