Trystar ULTRA-K Series 600K-he

Trystar ULTRA-K Series 600K-heThe Trystar ULTRA-K Series 600K-he, 5 kVA-25 kVA, single phase, high efficiency, K-rated power conditioning transformers meet and exceed DOE 2016 minimum efficiency standards.

The ULTRA-K Series 600K-he is a high efficiency, K-rated, power conditioning transformer, specifically designed to provide a high degree of electrical noise attenuation and transient voltage suppression to protect sensitive electronic loads. Offered with four different K-factor ratings (K4, K7, K13, and K20), the ULTRA-K is fully compatible with non-linear loads, handling the high harmonic currents associated with such loads.

Single phase models include nominal input voltage options from 208VAC to 600VAC, with (2) 2.5% voltage taps FCAN, and (4) 2.5% voltage taps FCBN. Output voltage options include 120VAC, 120/240VAC, or 208VAC.

The ULTRA-K is provided in a NEMA 2 enclosure, or optional NEMA 3R.

Trystar ULTRA-K Series 600K-he Features

  • Transformer power losses are lower than mandated by the DOE 2016 Standard, yielding a direct decrease in operating costs over the life of the transformer
  • Double or triple shielded for high common mode noise attenuation from input to output; and also prohibits system back feed from noise generating load
  • Optional output category B3 SPD (40kA per mode) with high frequency filter provides critical loads with optimum protection from noise, impulses, and high-energy voltage transients
  • Optional output SPD (50 kA to 200 kA per phase), UL 1449 Listed, Type 2, including EMI/RFI filtering, Form C relay contacts, and LED status indicators
  • Multiple K-factor ratings (K4, K7, K13, K20) allow proper application for both linear and non-linear loads. The higher the K-factor rating, the more harmonic current the transformer can handle
  • Designed specifically to handle the harmonics and heating effects created by non-linear loads
  • All-copper wound transformer construction allows the optimization of conductor size and geometry, to enhance harmonic-handling capability and transformer efficiency
  • Standard, floor mounted enclosure: NEMA 2; optional NEMA 3R outdoor enclosure available
  • Optional input and/or output circuit breaker(s) provided in a separate NEMA 1 enclosure for external mounting and installation
  • Optional high/over temperature alarm contacts provided for tripping upstream breakers if required
  • Optional industrial-grade IR scanning window(s) for safe, routine thermal scanning of transformer connections under load, without exposing personnel to arc flash hazards
  • Optional lug kit available – mechanical (screw-type) lugs shipped for installer convenience

Trystar ULTRA-K Series 600K-he Specifications

  • Efficiency: U.S. — Meets and exceeds U.S. Department of Energy (DOE) 2016 minimum efficiency standards identified under DOE 10 CFR Part 431
  • Canada — Meets and exceeds CSA Standard C802.2-12
  • Multiple Voltage Compensation Taps: Full capacity above/below nominal
  • Output Impedance: 2% – 3.5% typical
  • Output Distortion: Less than 1.0% THD added under linear load
  • Load Regulation: 2% typical, no load to full load
  • Overload: Up to 500% for 10 seconds, 1000% for 1 cycle
  • Isolated Neutral: Establishes a new neutral to ground bond on the transformer’s output
  • Common Mode Noise Attenuation: 126 dB (standard double shielding); 146 dB (optional triple shielding)
  • Transverse Mode Noise Attenuation: 3 dB down at 10kHz, decaying 20 dB per decade; decaying 40 dB with “SPD With High Frequency Filter” option
  • Operating Temperature: -25°C to +40°C
  • Audible Noise: 45 to 50 dBA @ 1 meter (kVA size dependent)
  • Temperature Rise: 135°C rise above ambient, under non-linear loading per UL 1561 standard
  • UL 1561 Listed, labeled for operation at or below a specific K-factor rating
  • C-UL Listed to CSA Standard C22.2, No 47-13

For more in-depth specifications, see the data sheet.

For more information about Trystar Power Products,
call 800-876-9373 or email [email protected].