The Power Experts

Eaton FERRUPS

Eaton Ferrups TowerThe Eaton FERRUPS Tower and Rackmount Series delivers proven, ferroresonant battery backup power and scalable runtimes for 911 centers, global military installations, marine vessels and other critical applications where downtime in unacceptable. Highly configurable with a wide range of voltages, frequencies, runtimes, power cords and receptacles, the Eaton FERRUPS continually regulates voltage and eliminates harmful harmonic currents.

Extensive configurability options make the FERRUPS an ideal, flexible power protection solution with a wide range of voltages, frequencies, runtimes, power cords and receptacles to fit your application. FERRUPS prevents the backfeed of harmonic currents into building wiring which can disrupt computer operations. Redundant power paths assure high fault-tolerance and optimum uptime. Galvanic isolation separates input from output, filtering line noise and surges. FERRUPS also features precision voltage regulation with no battery discharge down to 38% below nominal (depending upon the load) as well as over 80 user-programmable diagnostic and communications functions. Adaptable to virtually any application with customizable receptacles, input plugs, voltage-matching transformers and bypass switches.

Eaton FERRUPS Features

  • TAA Compliant – For use in government applications such as schools, courthouses, libraries and state facilities
  • Delivers bulletproof protection with Ferroresonant technology
  • Converts power from almost any AC source into computer-grade power
  • Prolongs backup time with external battery cabinets
  • Conditions incoming power without depleting the battery to preserve battery power for complete power outages
  • Adapts to virtually any application with customizable receptacles, input plugs, voltage-matching transformers and bypass switches
  • Ensures data integrity with free Software Suite bundle including LanSafe software and FORESEER network monitoring software

FERRUPS Specifications

Power Rating: 1150 VA to 18 kVA
Voltage: 120/208/240
Frequency: 60 Hz
Configuration: Tower or Rackmount

FERRUPS Models

Model Capacity Form Factor Input Output Runtime (min)
Full load/Half load
FE1.15 kVA 1.15kVA/.8kW, 120/208V Tower 6 ft. cord w/5-15P (6) 5-15R 8/22
FE1.4 kVA 1.4kVA/1kW, 120/208V Tower 6 ft. cord w/5-15P (6) 5-15R 11/31
FES1.4 kVA 1.4kVA /1kW, 120/208V Rackmount 120/50A HW 14/36
FE1.8 kVA 1.8kVA/1.25kW, 120/208V Tower 6 ft. cord w/5-20P (6) 5-15R 11/30
FE2.1 kVA 2.1kVA/1.5kW, 120/208V Tower 6 ft. cord w/5-20P (6) 5-15R 9/25
FER2.1 kVA 2.1kVA/1.5kW, 120/208V Rackmount 120/25A HW std. 24/58
FE3.1 kVA 3.1kVA/2.2kW, 120/208V Tower 6 ft. cord w/L5-20P (6) 5-15R 14/35
FER3.1 kVA 3.1kVA/2.2kW, 120/208V Rackmount 120/35A,
208/20A,
240/20A
HW std 14/35
FE4.3 kVA 4.3kVA/3kW, 120/208V Tower 120/40A, 208V/25A, 240V/20A HW std. 10/24
FE5.3 kVA 5.3kVA/3.7kW, 120/208V Tower 120/50A, 208V/30A, 240V/25A HW std. 20/50
FE7 kVA 7kVA/5kW, 120/208V Tower 120/70A, 208V/40A, 240V/35A HW std. 12/33
FER7 kVA 7kVA/5kW, 120/208V Rackmount 208/40A, 240/40A HW std 12/33
FE10 kVA 10kVA/7.5kW, 208V Tower 208V/60A, 240V/50A HW std. 11/26
FE12.5 kVA 12.5kVA/10kW, 208V Tower 208V/80A, 240V/70A HW std. 18/48
FE18 kVA 18kVA/15kW, 208V Tower 208V/110A, 240V/100A HW std. 10/26

For more in-depth information, see the model pages below or the following data sheets;
FERRUPS 60Hz Tower
FERRUPS 60Hz Rackmount

For more information on Eaton FERRUPS UPS,
c
all 800-876-9373 or email sales@power-solutions.com.