The Active Power CLEANSOURCE SMS PLUS UPS, is a modular flywheel system that offers low total cost of ownership, reliability, and sustainability for any mission critical application.
Designed with highly predictable, battery-free energy storage, the Single Module System (SMS) is based on Active Power’s Parallel Online Architecture which provides excellent isolation between input and output, while delivering Class 1 voltage regulation and dynamically cancelling effects of non-linear load harmonics.
This topology continuously provides online power protection to your data center, creating a clean sinusoidal output waveform and protecting critical operations against all 9 IEEE power disturbances in a power dense, reliable, and energy-efficient package. These models are made in the USA.
CLEANSOURCE SMS PLUS UPS Features
- Up to 98% efficient
- Parallel up to 8 systems
- Compact footprint, half the space of legacy battery based UPS
- Lower installation costs
- Lower cooling requirements
- Wide ambient temperature range, ideal for rugged applications
- Remote monitoring capability
- Generator compatibility
- 20-year design life
- Redundant fans and control power units
- Less required maintenance and service
- Color LCD touch-screen display
- Built-in power factor correction
- Integrated maintenance bypass option
Flywheel Technology Features
- Stores 6.2 MJ of energy; up to 2 minutes of runtime (load dependent)
- Wide ambient temperature range 32°F to 104°F and high density, high efficiency design
- Over 96% efficient at 40% load
- No need for dedicated cooling for batteries
- Routine annual check-up and bearing change every third year
- Integrated flywheel with 20-year life
CLEANSOURCE SMS PLUS UPS Specifications
| Rating | |
| Maximum kVA | 333 |
| Maximum kW | 300 |
| Input | |
| Voltage | 480 VAC 3-phase, 3-wire plus ground |
| Voltage Range | +10%/-15% (programmable) |
| Frequency | 60Hz |
| Power Factor | 0.99 at rated load and nominal voltage |
| Output | |
| Voltage | 480 VAC 3-phase, 3-wire plus ground |
| Voltage Regulation | Steady State: +/-1% for +/-10% input Flywheel Mode: +/-1% steady state Transient: +/-1% within 50mSec for 100% load step |
| Frequency | 60Hz |
| Current – Nominal 480VAC | 400A |
| Energy Storage | |
| Type | Integrated Steel Flywheel spinning at 10,000RPM |
| Flywheel Run Time | 100%: 20s 75%:27s 50%: 39s 25%: 73s |
| Flywheel Recharge Time | ˂3 min nominal at 65kW |
| Internal Static Bypass | Included |
| Operating Temperature | 32 to 104°F |
| Height | 78 in. |
| Width | 58.6 in. |
| Depth | 34.1 in. |
| Weight | 4,598.8 lbs. |
| Cable Entry | Top or Bottom |