Trystar MedPoweRx UPS Model LT/M

UPS Systems | Trystar UPS Systems | Trystar MedPoweRx UPS Model LT/M

Trystar MedPoweRx UPS Model LT/MThe Trystar MedPoweRx UPS Model LT/M, 700VA – 2.1kVA, medical grade UPS is a single phase, seamless transfer, UL 60601-1 listed, UPS for use with patient vicinity medical equipment, such as fluoroscopy, patient monitors, ultrasound, and other critical medical equipment. The Model LT/M not only protects sensitive medical equipment from power outages, but it also regulates voltage, attenuates harmonics, and eliminates line and ground noise. The Model LT/M is certified as meeting NFPA 99 leakage current requirements for portable patient vicinity equipment.

Trystar MedPoweRx UPS Model LT/M Features

  • Continuous, uninterrupted sinewave output with less than 3% harmonic distortion, any single harmonic
  • Less than 300 micro-amps leakage current reduces the electric shock hazard in case of a loss of ground condition
  • (3) NEMA 5-20R2 (5-15R2 for Canada) duplex medical-grade output receptacles
  • Built-in isolation protects the load from damaging power disturbances
  • “Cold start” feature for mobile operations
  • Numeric, 3-digit LED, display panel identifies system status and alarm conditions
  • Serial communication and contacts for remote monitoring of system status and alarms
  • Optional NetMinderTM software for remote monitoring of electrical parameters, system status and alarms, as well as unattended shutdown of system computer or network server
  • Optional specially-designed wheeled cart enables UPS portability

Trystar MedPoweRx UPS Model LT/M Specifications

  • Input Operating Voltage: 120VAC
  • Input Operating Voltage Range: +10%, -30% typical, load-dependent, without battery usage
  • Input Current THD: < 3%
  • Leakage Current to Ground: < 300μA
  • Output Voltage Regulation: +/- 3%
  • Load Regulation: Typically better than +/- 3%
  • Overload Capability: 125% for 10 minutes
  • Surge Capability: 150% of rated output
  • Operating Temperature: 0°C to 40°C
  • Common Mode Noise Attenuation: 120dB
  • Transverse Mode (Line) Noise Attenuation: 70dB
  • Spike Attenuation: 3000:1
  • Crest Factor: 3.5:1

For more in-depth specifications, see the data sheet.

For more information about Trystar UPS Systems,
call 800-876-9373 or email [email protected].