Trystar Model LTN

UPS Systems | Trystar UPS Systems | Trystar Model LTN

Trystar Model LTNThe Trystar Model LTN UPS, 700VA – 2.1kVA, with a drip-proof enclosure is designed to NEMA 2 standards and provided on channels for floor mounting. Optional wall-mounting brackets are available.

Within each Model LTN UPS is a rugged constant voltage transformer which provides output line voltage regulation of ±3%. In addition, magnetic isolation, filtering, and power conditioning provide ultimate protection from extreme power line disturbances and power outages. 

Trystar Model LTN Features

  • No break, regulated, continuous sine wave output
  • Integral constant voltage transformer isolates and regulates output voltage
  • NEMA 2 drip-proof enclosure design
  • Status and alarm panel, with optional remote status panel
  • Internal battery options, providing extended runtimes from 30 minutes to 7 hours at full load, model dependent
  • Input breaker and output breakers (up to 6 single pole positions total)
  • Output circuit breaker monitor option
  • Standard 3 amp or optional 8.5 amp battery charger
  • Key-lockable front door
  • Front access design
  • Generator compatible
  • Remote communications via alarm signals or RS232.
  • Optional four (4) isolated sets of status & alarm relay contacts.
  • Optional NetMinder™ remote monitoring via Ethernet TCP/IP, MODBUS TCP, or MODBUS RS485
  • Optional wall mounting kit
  • Input and output main circuit breakers
  • Flush-mounted status and alarm panel
  • Optional 8.5 amp accelerated, temperature-compensated battery charger

Trystar Model LTN Specifications

  • Input Operating Voltage Range: +10%, -40% typical, load-dependent, without battery usage
  • Input Frequency: 60 Hz, ± 2.5 Hz
  • Output Sine wave Voltage: Maximum 3% harmonic distortion, any single harmonic
  • Voltage Regulation: ± 3% typical
  • Isolation: Galvanic
  • Operating Temperature: 0° C to 40° C (32° F to 104° F)
  • Total System MTBF: 100,000 hours
  • Common Mode Noise Attenuation: 120 dB
  • Transverse Mode Noise Attenuation: 70 dB
  • Efficiency: 89% typical

For more in-depth specifications, see the data sheet.